LP1250(1250KVA)Genrator Specification
Rating |
Prime Power – KW(KVA),1000 (1250) |
||
Load |
50% |
75% |
100% |
Liters/ hr |
139 |
199 |
259 |
g/Kwh |
215 |
204 |
199 |
Engine |
Prime Power Rating |
Engine Manufacturer |
Perkins UK |
Engine Model |
4012‐46TAG0A |
Configuration |
12 'Vee' |
Aspiration |
Turbo Charged and After Cooled |
Gross Engine Power output kWm / BHP |
1053 / 1412 |
Net Engine power output kWm / BHP |
1117 / 1497 |
BMEP @ rated load , kPa |
1949 |
Displacement , L |
45.842 |
Bore , mm |
160 |
Stoke, mm |
190 |
Rated Speed, rpm |
1500 |
Piston Speed, m/s |
9.5 |
Compression Ratio |
13.6 : 1 |
Lub oil capacity Max, L |
159 |
Lub oil capacity Min, L |
136 |
Governor Type |
Electronics |
Starting Voltage, V‐ DC |
24 |
Recommended fuel to conform to |
BS2869 1998 Class A2 or BS EN590 |
Type of injection system |
Direct injection |
Fuel injection pump |
Combined unit injector |
Fuel injector |
Combined unit injector |
Fuel injector pressure, bar |
1400 |
Fuel lift pump |
Tuthill TCH 1‐089 |
Delivery at 1500 rev/min, L/hr |
1020 |
Heat retained in fuel to tank, kW |
8 |
Fuel Inlet Temperature to be less than, °C |
58 |
Delivery pressure, kPa |
300 |
Maximum suction head at pump Inlet , m |
2.5 |
Fuel filter spacing, microns |
10 |
Tolerance on fuel consumption, % |
5 |
- Governing to ISO8528‐12 Class 3 & 4: ISO8528‐5 ClassG2
Air
Maximum air intake restriction of engine clean filter |
2 kPa |
Maximum air intake restriction of engine , dirty filter |
4 kPa |
air filter type |
cylinder paper pleat |
Combustion air flow m³/min |
106 |
Exhaust
Maximum back pressure for total system |
5 kPa |
Exhaust gas temperature, after turbo °C |
425 |
Exhaust gas flow maximum, after turbo , m³/min |
280 |
Standard set –mounted radiator cooling
Ambient design, °C |
52 |
Fan Load , KW |
64 |
Coolant Capacity with radiator , Lit |
210 |
Engine Coolant Flow Lit/min |
1020 |
cooling system air flow ‐ m³/sec |
32.4 |
Weights* |
open |
Unit dry weight kgs |
8514 |
Unit wet weight kgs |
10200 |
- Weight represent a set with standard feature
Dimension |
Length |
Width |
Height |
Standard open set dimension |
5300 |
2000 |
2800 |
Test conditions
Air temperature 25 °CBarometric pressure 100 kPa
Relative humidity 30%
Air inlet restriction at maximum power (nominal) 2.5 kPa
Exhaust back pressure (nominal) 3.0 kPa
Alternator
Specification 1250kVA ‐ 3phModel PI734B1
Rated Voltage 415V
Type 4 pole
Exciter type Brushless
Insulation Class ‐ H
Temperature rise 125 °C
Enclosure Protection IP23
Bearing Single
Voltage regulation ± 0.5%
Efficiency 94.8